冬季供暖工況下混凝土輻射頂板傳熱特性

2016-05-31 10:07李敬李念平孫亞芬蘇林張絮涵
土木建筑與環境工程 2016年2期
關鍵詞:數學模型

李敬 李念平 孫亞芬 蘇林 張絮涵

摘要:針對冬季供暖工況下混凝土輻射頂板的傳熱問題,建立頂板輻射供暖的簡化數學模型,利用MATLAB軟件計算其供熱量,并通過該頂板輻射供暖的熱工特性實驗驗證模型的合理性。研究表明:頂板溫度計算值與實驗結果的誤差在5.01%以內,供熱量計算值與實驗結果的誤差在515%左右。通過對實驗和計算結果的分析發現:在定流量穩態工況下,頂板溫度隨供水溫度的增大呈指數性增大,隨換熱盤管間距的增大而減小。

關鍵詞:輻射供暖;傳熱;供熱量;數學模型;實驗驗證

中圖分類號: TU832.1

文獻標志碼:A 文章編號:16744764(2016)02011807

Abstract: A simplified mathematical model was established to calculate the heating transfer capacity through MATLAB program. Compared with the results of thermal performance test, the mathematical model was reasonable with a maximum error less than 5.15%. According to the results of model and experiment, in the constant flow condition, heating capacity of the ceiling increases as the temperature increases, meanwhile heating capacity decreases as the heat exchange coil spacing increases.

Keywords:ceiling radiant heating panel; heat transfer; heating capacity; mathematic model; experimental validation

輻射板空調系統以其節能、環保、低噪聲[1]、房間無明顯吹風感[2] 、熱舒適性高[3]及節省建筑空間等優點逐漸成為人們新的選擇,與傳統空調相比可節省全年能耗30%以上[4]。2002年美國能源部將其作為未來最有優勢的15項暖通空調節能技術之一[5]?,F代空調技術起源于歐洲,20世紀70年代瑞士率先推出用于低溫地板輻射采暖的交聯聚乙烯管材,大大促進了輻射采暖空調的發展[6],20世紀80年代末,低溫地板采暖技術已經被廣泛應用于住宅以及商場、飯店等民用及公共建筑,20世紀90年代初魯諾·凱勒教授設計的混凝土頂板輻射采暖制冷成功運行,使建筑集供冷采暖為一體技術得以實現,減少了設備占有建筑空間和設備初投資。目前,可采用加隔熱保溫層等措施來降低混凝土背面的熱損失,降低建筑結構內外溫差。如果是高層建筑,對每一層的室內來講,相當于地面和頂面雙層供暖,混凝土樓板具有較大蓄熱能力,較低的供水溫度就可滿足人體熱舒適要求,因此,混凝土輻射板供暖逐步得到應用。2013年李嚴在長沙萬國城,做了混凝土頂板雙面輻射供暖傳熱的模擬研究[7]。與此同時,學者們也致力于輻射板換熱量的研究,Davie等[8]提出輻射換熱平均輻射溫度模型,Maloney等[9]提出輻射供暖計算模型等。

目前,研究主要集中在夏季工況混凝土頂板供冷上,而對冬季工況混凝土頂板輻射供暖傳熱性能較少,不利于實現建筑混凝土頂板輻射供暖制冷一體化。

筆者首先建立簡化數學模型,利用MATLAB軟件計算混凝頂板換熱量,然后通過實驗對模型進行驗證,同時研究不同管間距時室內溫度的垂直分布、換熱量等頂板輻射特性。

1 混凝土頂板傳熱數學模型

1.1 模型假設

為了方便求解,對混凝土頂板的傳熱做出以下簡化[10]:

1)在穩態工況下分析所有傳熱過程。

2)由于輻射頂板埋管上設有保溫層,故可忽略頂板背面的傳熱,即輻射板為單面傳熱。

3)換熱盤管內的熱媒均為均勻流動。

4)在模型中,假設水溫沿單位管長無變化,忽略沿管軸線方向導熱;混凝土頂板表面的溫度分布符合肋片溫度分布規律,埋管導熱可看為等截面直肋的導熱。

如圖1所示,頂板表面溫度分布符合肋片溫度分布規律,管頂混凝土頂板表面溫度最高(tmax),將其視為肋基,兩管道之間表面溫度最低(tmin),將管道之間2W區域視為肋片。由于混凝土輻射頂板中管道—般采用等間距平行布置,可近似認為兩管之間對稱。

2 混凝土輻射頂板熱工特性實驗

2.1 實驗搭建

實驗對象為位于長沙的一間混凝土頂板輻射供暖熱工實驗室如圖2[15]所示。該實驗室主要為測試混凝土頂板熱工性能而設計,可創造一個可控且不受外界干擾的實驗環境。為模擬住宅混凝土頂板輻射供熱環境該試驗室分為上下兩層,其中一層尺寸為(長×寬×高)1 560 mm×1 560 mm×1 510 mm,西外窗尺寸720 mm×510 mm,僅供實驗人員進出試驗室,實驗中小窗采用擠塑聚苯板密封?;炷另敯鍢嬙鞂影ɑ炷翆蛹皳Q熱盤管如圖3所示。為防止室外溫濕度對實驗室的干擾,頂板設置20 mm厚的擠塑苯板,墻體設置200 mm厚的低導熱系數的加氣混凝土砌塊,地板底部設置200 mm厚的低導熱系數的加氣混凝土砌塊,實驗室各物性參數見表1。為研究不同管間距對頂板輻射換熱量的影響,實驗室頂部采用150/300 mm兩種間距換熱盤管如圖4,換熱盤管距混凝土頂板下表面距離40 mm。

2.2 測量參數及儀器

實驗測試參數主要包括供回水溫度、供水流量、室內空氣溫度和相對濕度、混凝土頂板溫度、各個非供暖圍護結構的溫度、室外空氣溫度及頂板換熱量等。實驗每隔30 s采集一次數據,為減少實驗誤差,采取多點測量連續記錄取平均值的方法?;炷另敯搴偷匕甯鞑贾?個點,墻體布置3個點,測點分布如圖5和圖6所示;在試驗臺中間距地面分別為0.4、0.8、1.2、1.4 m的位置處布置4個溫度測量點,實驗所用的測量儀器如表2所示。

2.3 實驗內容

該實驗水系統采用定流量變溫度控制方法,通過控制供回水溫度來調節混凝土頂板表面溫度。試驗中,為避免流量變化對頂板供熱量影響,熱媒流量設定為0.40 m3/h。改變供回水溫度使輻射頂板溫度在30.4~37.5 ℃之間變化。穩態工況下每30 s記錄一組數據,得到頂板輻射供暖工況下的熱工參數,求出混凝土頂板輻射換熱量,驗證上述數學模型的正確性。

3 數學模型驗證及實驗分析

1)從表3和圖7中可以看出,混凝土頂板溫度傳熱模型的驗證包括2個方面,針對模型中的未知量:頂板下表面平均溫度和頂板單位面積供熱量可測量得到。表3為6種供水溫度工況下,2種不同換熱盤管間距實驗測量值與數學模型計算值對比,從表中可以看出模型供熱量的計算誤差在5.15%之內,頂板溫度的誤差小于5.01%,因此,計算模型基本與實驗相吻合。由于實驗過程中試驗臺并不是完全與外界隔絕,且熱媒沿換熱盤管方向溫度降低,因此,混凝土頂板輻射供熱數學模型的供熱量小于實驗值,在相同工況下,150 mm的換熱盤管間距頂板溫度比300 mm換熱盤管間距大,隨著供水溫度增大,頂板溫度呈指數增大。

2)從圖8可看出,在供水溫度相同的情況下,管間距越小,頂板換熱量越大,頂板溫度分布越均勻,更容易達到室內的設計溫度,增加房間舒適性。如果要求較大的管間距,可以通過提高供水溫度溫度來滿足房間溫度要求,但是這樣不僅增加供熱系統的能耗,還由于頂板溫度分布不均勻造成室內舒適性降低。

5 結 論

1)針對頂板輻射供暖換熱量計算問題,建立簡化平面肋片法模型,理想實驗條件下模型計算值與實驗測量值誤差在5.15%以內,實際工況實驗下模型計算值與實驗測量值誤差在7.66%左右,滿足系統設計要求。

2)混凝土頂板輻射采暖在供水溫度一定的條件下,隨著盤管間距的增加,混凝土頂板表面溫度和熱流密度都會降低。

3)實驗得知:供水溫度在37.5 ℃~41.5 ℃時,0.4 m與1.2 m處室內空氣溫度差在3 ℃左右。

參考文獻:

[1] 王子介.低溫輻射供暖和輻射制冷[M].北京:機械工業出版社,2004.

WANG Z J. Lowtemperature radiant heating and radiant cooling[M].Beijing: Mechanical Industy.(in Chinese)

[2] REES S J,HAVES P.An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling[J].Building and Environment, 2013,59:358368.

[3] ANDRSCHICOTE M,TEJEROGONZLEZ A,VELASCOGMEZ E,et al.Experimental study on the cooling capacity of a radiant cooled ceiling system[J].Energy and Buildings,2012,54:207214.

[4] 宣永梅, 王海亮, 黃翔. 地板輻射與置換通風空調系統運行參數[J]. 土木建筑與環境工程, 2012, 34(6): 115119.

XUAN Y M,WANG H L, HUANG X. Operational parameters of hybrid radiation cooling floor and displacement ventilation air conditioning system [J].Journal of Civil, Architectural & Environmental Engineering, 2012,34(6):115119.(in Chinese)

[5] 壽青云. 輻射供冷空調方式能耗與控制的研究[D]. 上海: 同濟大學, 2009.

SHOU Q Y. The research for radiation cooling and air conditioning [D].Shanghai: Tongji University,2009.(in Chinese)

[6] MIRIEL J, SERRES L, TROMBE A.Radiant ceiling panel heatingcooling systems: experimental and simulated study of the performance, thermal comfort and energy consumptions[J].Applied Thermal Engineering, 2002, 22(16):l8611866.

[7] 李嚴. 混凝土頂板輻射空調系統換熱特性研究[D]. 長沙:湖南大學,2013.

LI Y. The research on heat transfer characteristics of concrete ceiling radiant airconditioning system.[D].Changsha University,2013.(in Chinese)

[8] DAVIE M. On the basis of environmental procedures[J].Building and Environment, 2001, 13(1):2024.

[9] MALONEY D. Development of irradiant heating systems model forblast[J].Building and Environment, 1988,88(24):17951808.

[10] 馬玉奇,劉學來,李永安,等.冷卻頂板空調系統的分析計算[C]// 中國制冷學會2007學術年會論文,2007:342346.

MA Y Q, LIU X L, LI Y A,et al. The analysis and calculation of ceiling radiant panel air conditioning system [C] .Chinese Refrigeration Association,2007:342346. (in Chinese)

[11] SUI X E, ZHANG X. Effects of radiant terminal and air supply terminal devices on energy consumption of cooling load sharing rate in residential buildings[J].Energy and Buildings, 2012, 49(10):499508.

[12] 劉艷峰.地板供暖設計與運行基礎理論研究[D].西安:西安建筑科技大學,2004.

LIU Y F. Study on Basic theroy of designing and ruanning control imbed pipe floor heating[D].Xian University of Architecture and Techology,2004. (in Chinese)

[13] KILKIS B: Enhancement of heat pump performance using radiant floor heating systems[J]. ASM,1992,28:119129.

[14] 章熙民, 任澤霈, 梅飛鳴, 等.傳熱學[M]. 北京:中國建筑工業出版社,2007, 169170.

ZHANG X M, REN Z P, MEI F M,et al. Heat transfer[M].Beijing: Chinese Building Industy Press,2007,169170.

[15] SU L, LI N P, ZHANG X H.Heat transfer and cooling characteristics of concrete ceiling radiant cooling panel [J].Applied Thermal Engineering, 2015,32(9):211221.

[16] 朱穎心,彥啟森. 建筑環境學[M]. 北京:中國建筑工業出版社,2009,104105.

ZHU Y X, YAN Q S. Building environment [M]. Beijing: Chinese Building Industy Press ,2009,104105.